CADDX NX-8e Specifikace

Procházejte online nebo si stáhněte Specifikace pro Bezpečnostní systémy pro řízení přístupu CADDX NX-8e. CADDX NX-8e Specifications Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk

Shrnutí obsahu

Strany 1 - Series

NetworX™ Series NX-8E Control Panel Installation and StartupUL approved for ANSI/SIA CP-01-2000

Strany 2 - SAFETY SYMBOL LEGEND

NX-8E CONTROL 8 IV. PROGRAMMING THE LED KEYPADS This section describes how to program the address and partition of each keypad as well as the option

Strany 3 - Table of Contents

NX-8E CONTROL 9CHANGING USER CODES: 1) Enter [r]-[5]-[master code] - The "Ready" LED will flash. 2) Enter the 3 digit user number (i.e.

Strany 4 - ORDERING INFORMATION

NX-8E CONTROL 10 V. PROGRAMMING THE CONTROL ENTERING THE PROGRAM MODE To enter the Program Mode, press [r]-[8]. At this time, the five function LEDs

Strany 5 - II. BOARD INSTALLATION

NX-8E CONTROL 11PROGRAMMING EXAMPLE - FIGURE 1 (Numerical Data) Zone 1 LED = 1 Zone 4 LED = 8 } Data = 9 To change data in a segment, enter the data

Strany 6 - III. GLOSSARY

NX-8E CONTROL 12 VI. PROGRAMMING DATA Programming data is always one of two types. One type of data is numerical and can take on values from 0 to 15 o

Strany 7

NX-8E CONTROL 13X. PROGRAMMING LOCATIONS L LOCATION 0 – PROGRAMMING PHONE NUMBER #1 (20 segments, numerical data) The first telephone number is pr

Strany 8

NX-8E CONTROL 14 reporting. Programming a "1" in this segment will cause the NX-8E to stop trying to communicate after the designated number

Strany 9

NX-8E CONTROL 15L LOCATION 8 - COMMUNICATOR FORMAT FOR PHONE # 2 (1 segment, numerical data) Location 8 contains the communicator format used to t

Strany 10 - NX-8E CONTROL

NX-8E CONTROL 16 LOCATION 11 - PARTITIONS REPORTED TO PHONE #2 (1 segment, feature selection data) Location 11 is used when events to be reported to

Strany 11

NX-8E CONTROL 17LOCATION 16 - EVENTS REPORTED TO PHONE #3 (2 segments, feature selection data) Segment 1: 1 = Alarms and Alarm Restores. 2 = Openi

Strany 12 - V. PROGRAMMING THE CONTROL

© 2005 GE Security All rights reserved. These instructions do not purport to cover all details or variations in equipment nor to provide every pos

Strany 13 - (Feature Selection Data)

NX-8E CONTROL 18 L LOCATION 21 - DOWNLOAD CONTROL (1 segment, feature selection data) Location 21 contains the feature selections for the controlli

Strany 14 - L QUICK START INSTALLATION

NX-8E CONTROL 19Segment 4: 1 – On enables Late to Close / Early to Open. 2 – On enables Auto Arm in Stay Mode. 3 – On disables the door delays in

Strany 15 - X. PROGRAMMING LOCATIONS

NX-8E CONTROL 20 DATA DESCRIPTION OF DEFAULT ZONE TYPES 15 INTERIOR FOLLOWER WITH GROUP BYPASS ENABLED - This zone will be instant when the system is

Strany 16

NX-8E CONTROL 21L LOCATION 27 - ZONES 9-16 ZONE TYPE (8 segments, numerical data) Location 27 contains the Zone Type for zones 9 -16. Segment 1

Strany 17

NX-8E CONTROL 22 L LOCATION 35 - ZONES 41-48 ZONE TYPE (8 segments of numerical data) Location 35 contains the Zone type for zones 41-48. Segment

Strany 18

NX-8E CONTROL 23Segment 6: 1 = Enable 2 wire smoke. 2 = Reserved. 3 = Enable for Zone Activity in Hours (not Days) 4 = Enable Daylight S

Strany 19

NX-8E CONTROL 24 L LOCATION 42 - GO TO PROGRAM CODE (6 segments, numerical data) Location 42 contains the "Go To Program Code". This loca

Strany 20

NX-8E CONTROL 25LOCATION 47 - AUXILIARY OUTPUT #1, EVENT AND TIME (2 segments, numerical data) Segment 1: Use Table XI-1 on page 25 to select the

Strany 21

NX-8E CONTROL 26 L LOCATION 51 - AUTOTEST CONTROL (4 segments, numerical data) Segment 1: Program a "1" if the interval is to be in hou

Strany 22

SLOW COMMUNICATOR FORMAT CODES NX-8E CONTROL 27LOCATIONS 56- 83 ARE ONLY USED WHEN REPORTING EVENTS TO A PAGER OR USING A SLOW FORMAT SUCH AS 4+2. W

Strany 23

NX-8E CONTROL 1Table of Contents I. GENERAL DESCRIPTION...

Strany 24 - NOTE: Must

SLOW COMMUNICATOR FORMAT CODES NX-8E CONTROL 28 LOCATION 64 - KEYPAD AUXILIARY 2 COMMUNICATOR CODE (2 segments, numerical data) Location 64 contains

Strany 25

SLOW COMMUNICATOR FORMAT CODES NX-8E CONTROL 29LOCATION 74 - EXPANDER TROUBLE / EXPANDER TROUBLE RESTORE COMMUNICATOR CODES (4 segments, numerical

Strany 26

NX-8E CONTROL 30 LOCATIONS 88-109 ARE FOR PROGRAMMING DIFFERENT ACCOUNT CODES AND/OR FEATURES FOR EACH PARTITION. IF A LOCATION IS LEFT

Strany 27

NX-8E CONTROL 31LOCATION 95 - ACCOUNT CODE FOR PARTITION 4 (6 segments, numerical data) The account code sent when partition 4 is reported is progra

Strany 28

NX-8E CONTROL 32 LOCATION 103 - PARTITION 6 ENTRY EXIT TIMERS (6 segments, numerical data) Location 103 is used to enter in seconds the Entry and Ex

Strany 29

NX-8E CONTROL 33LOCATIONS 110-169 ARE USED TO CHANGE THE ZONE TYPES (Configurations) AS LISTED IN THE TABLE ON PAGE 19. THESE LOCATIONS ARE CONSIDERE

Strany 30

NX-8E CONTROL 34 LOCATION 116 - ZONE TYPE 4 ALARM EVENT CODE (1 segment, numerical data) Location 116 contains the event code sent for a Contact ID

Strany 31

NX-8E CONTROL 35LOCATION 132 - ZONE TYPE 12 ALARM EVENT CODE (1 segment, numerical data) Location 132 contains the event code sent for a Contact ID

Strany 32

NX-8E CONTROL 36 LOCATION 146 - ZONE TYPE 19 ALARM EVENT CODE (1 segment, numerical data) Location 146 contains the event code sent for a Contact ID

Strany 33

NX-8E CONTROL 37LOCATION 160 - ZONE TYPE 26 ALARM EVENT CODE (1 segment, numerical data) Location 160 contains the event code sent for a Contact ID o

Strany 34

NX-8E CONTROL 2 ORDERING INFORMATION PART # DESCRIPTION NX-8E NX-8E Control Only NX-848E-KIT NX-8E Control, NX-148E LCD Keypad, 16.5V 40VA Trans

Strany 35

NX-8E CONTROL 38 LOCATION 173 - PARTITION SELECT, ZONES 57-64 (8 segments of feature selection data) Location 173 is used to select the partition(s

Strany 36

NX-8E CONTROL 39LOCATION 181 - PARTITION SELECT, ZONES 89-96 (8 segments of feature selection data) Location 181 is used to select the partition(s)

Strany 37

NX-8E CONTROL 40 Segments 1 - 8: 1 = Partition #1 3 = Partition #3 5 = Partition #5 7 = Partition #7 2 = Partition #2 4 = Partition #4 6 = Parti

Strany 38

NX-8E CONTROL 41L LOCATION 198 - ZONES 161-168 ZONE TYPE (8 segments, numerical data) Location 198 contains the Zone Type for zones 161-168. Seg

Strany 39

NX-8E CONTROL 42 LOCATION 206 – AUTO DISARM DAY SELECTOR (8 segments of feature selection data) Location 206 selects which days each partition will

Strany 40

NX-8E CONTROL 43LOCATION 211 - PROGRAMMING THE COMMAND/REQUEST ENABLES (4 segments of feature selection data) The NX-8E has the ability to perform a

Strany 41

NX-8E CONTROL 44 LOCATION 212 - PROGRAMMING THE LCD KEYPAD ADDRESS (1 segment of numerical data) Certain commands in the NX-8E require it to know th

Strany 42

NX-8E CONTROL 45XII. PROGRAMMING WORKSHEETS (Factory defaults for segments are in bold italics text and "Quick Start" locations are identif

Strany 43

NX-8E CONTROL 46 LOC PG DESCRIPTION DEFAULT PROGRAMMING DATA 14 16 PHONE #3, REPORTING FORMAT 0 _ 15 16 PHONE #3, DIAL ATTEMPTS BACKUP CO

Strany 44 - Default is OFF

NX-8E CONTROL 47LOC PG DESCRIPTION DEFAULT PROGRAMMING DATA L 23 18 PARTITION #1, FEATURE SELECTION Segment #1 1 = Quick Arm 2 = Re-Exit 3 =

Strany 45

NX-8E CONTROL 3I. GENERAL DESCRIPTION The NetworX NX-8E represents a new approach to security systems design. Drawing on our experience in the worl

Strany 46

NX-8E CONTROL 48 LOC PG DESCRIPTION DEFAULT PROGRAMMING DATA L 29 21 ZONES 17-24, ZONE TYPES 6-6-6-6-6-6-6-6 _ _ _ _ _ _ _ _ ZONES 17-24

Strany 47 - XII. PROGRAMMING WORKSHEETS

NX-8E CONTROL 49 LOC PG DESCRIPTION DEFAULT PROGRAMMING DATA SIREN AND SYSTEM SUPERVISION Segment #1 (Circle numbers to program) L 37 22 1 2 3

Strany 48

NX-8E CONTROL 50 LOC PG DESCRIPTION DEFAULT DATA L 38 23 SWINGER SHUTDOWN COUNT 1 _ KEYPAD SOUNDER CONTROL Segment #1 (Circle numbers to progra

Strany 49

NX-8E CONTROL 51 LOC PG DESCRIPTION DEFAULT DATA Segment #2 (Circle numbers to program) 43 24 1 2 3 4 5 6 7 8 Enables "Go To Pro

Strany 50

NX-8E CONTROL 52 LOC PG DESCRIPTION DEFAULT DATA OPENING TIME Segment #1: Program the hour of the opening time. 8 52 26 Segment #2: Program

Strany 51

NX-8E CONTROL 53LOC PG DESCRIPTION DEFAULT DATA 57 BYPASS COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY Segment #1: Partition #1 Bypass

Strany 52

NX-8E CONTROL 54 LOC PG DESCRIPTION DEFAULT DATA 69 28 LOW BATTERY / LOW BATTERY RESTORE 0-0-0-0 _ _ _ _ 70 28 POWER SHORT / POWER SHORT R

Strany 53

NX-8E CONTROL 55 LOC PG DESCRIPTION DEFAULT DATA PARTITION 2 ENTRY/EXIT TIMERS Segment #1 (Entry Time #1) 0 _ Segment #2 (Exit Time #1) 0 _ S

Strany 54

NX-8E CONTROL 56 LOC PG DESCRIPTION DEFAULT DATA PARTITION 4, ENTRY/EXIT TIMERS Segment #1 (Entry Time #1) 0 _ Segment #2 (Exit Tim

Strany 55

NX-8E CONTROL 57LOC PG DESCRIPTION DEFAULT DATA PARTITION 6, ENTRY/EXIT TIMERS Segment #1 (Entry Time #1) 0 _ Segment #2 (Exit Tim

Strany 56

NX-8E CONTROL 4 III. GLOSSARY Abort - If enabled, the NX-8E will wait the programmed number of seconds in location 40 prior to sending an alarm. Duri

Strany 57

NX-8E CONTROL 58 LOC PG DESCRIPTION DEFAULT DATA PARTITION 8, ENTRY/EXIT TIMERS Segment #1 (Entry Time #1) 0 _ Segment #2 (Exit Ti

Strany 58

NX-8E CONTROL 59LOC PG DESCRIPTION DEFAULT DATA 130 34 ZONE TYPE 11 ALARM EVENT CODE 3 __ 131 34 ZONE TYPE 11 CHARACTERISTIC SELECT 3-0-0-0-

Strany 59

NX-8E CONTROL 60 LOC PG DESCRIPTION DEFAULT DATA L172 37 ZONES 57-64, ZONE TYPES 6-6-6-6-6-6-6-6 _ _ _ _ _ _ _ _ ZONES 57-64, PARTIT

Strany 60

NX-8E CONTROL 61 LOC PG DESCRIPTION DEFAULT DATA L180 38 ZONES 89-96, ZONE TYPES 6-6-6-6-6-6-6-6 _ _ _ _ _ _ _ _ ZONES 89-96, PARTIT

Strany 61

NX-8E CONTROL 62 LOC PG DESCRIPTION DEFAULT DATA L188 39 ZONES 121-128, ZONE TYPES 6-6-6-6-6-6-6-6 _ _ _ _ _ _ _ _ ZONES 121-128, PA

Strany 62 -

NX-8E CONTROL 63 LOC PG DESCRIPTION DEFAULT DATA L196 40 ZONES 153-160, ZONE TYPES 6-6-6-6-6-6-6-6 _ _ _ _ _ _ _ _ ZONES 153-160, PAR

Strany 63

NX-8E CONTROL 64 LOC PG DESCRIPTION DEFAULT DATA L204 41 ZONES 185-192, ZONE TYPES 6-6-6-6-6-6-6-6 _ _ _ _ _ _ _ _ ZONES 185-192, PA

Strany 64

NX-8E CONTROL 65 NX-584 COMMAND/REQUEST ENABLE Segment #1 Segment #2 1 = Reserved 2 = Interface Configuration Request 3 = Reserved 4 = Zone Name Req

Strany 65

NX-8E CONTROL 66 XIII. NX-8E WIRING DIAGRAM

Strany 66

NX-8E CONTROL 67XIV. TERMINAL DESCRIPTIONS TERMINAL DESCRIPTION R1 House Telephone Ring (Grey). R Telephone Ring (Red). T Telephone Tip (Green).

Strany 67

NX-8E CONTROL 5Communication Formats- The NX-8E can report in multiple formats. It is recommended that you use Contact ID or SIA formats if possible.

Strany 68 - XIII. NX-8E WIRING DIAGRAM

NX-8E CONTROL 68 ZONE WORKSHEET 1 49 97 145 2 50 98 146 3 51 99 147 4 52 100 148 5 53 101 149 6

Strany 69 - XIV. TERMINAL DESCRIPTIONS

NX-8E CONTROL 69XV. APPENDIX 1 REPORTING FIXED CODES IN CONTACT ID AND SIA The table lists the event codes sent for the following reports (if enabl

Strany 70

NX-8E CONTROL 70 XVI. APPENDIX 2 REPORTING ZONE CODES IN SIA OR CONTACT ID The NX-8E has the ability to report SIA level 1 transmissions to either

Strany 71 - XV. APPENDIX 1

NX-8E CONTROL 71XVII. APPENDIX 3 EXPANDER NUMBERS FOR REPORTING EXPANDER TROUBLE The tables below list the device numbers that will be reported for

Strany 72 - XVI. APPENDIX 2

NX-8E CONTROL 72 XVIII. APPENDIX 4 USER ID OR ZONE ID HEX DIGIT FOR 4+2 FORMATS The following appendix applies only to slow formats (locations 56- 8

Strany 73 - XVII. APPENDIX 3

NX-8E CONTROL 73XIX. TELEPHONE COMPANY INTERFACE INFORMATION TELEPHONE CONNECTION REQUIREMENTS Except for telephone company provided ringers, all c

Strany 74 - XVIII. APPENDIX 4

NX-8E CONTROL 74 XX. NOTICES (Applies to products which have the CE mark attached) DECLARATION OF CONFORMITY Manufacturer’s Name: Caddx Control

Strany 75 - INDUSTRY CANADA INFORMATION

NX-8E CONTROL 75XXI. UNDERWRITERS LABORATORIES INFORMATION The NetworX NX-8E holds the following listings from Underwriters Laboratories (US and Can

Strany 76 - XX. NOTICES

NX-8E CONTROL 76 MINIMUM SYSTEM CONFIGURATIONS FOR UL INSTALLATIONS (Residential Fire, Residential Burglary, Commercial Burglary) • The NetworX NX-

Strany 77 -  Hochiki: SBC-4/12, 4/12W

XXII. SIA SYSTEM REQUIREMENTS (ANSI / SIA CP-01) Important Note: UL requirements take priority over SIA requirements To meet SIA CP-01 requirement

Strany 78 - ALARM CURRENT

NX-8E CONTROL 6 Group Bypass - A designated group of zones can be programmed to bypass by pressing [Bypass]- [0]-[Bypass]- [Bypass] prior to arming.

Strany 79

XXIII. SPECIFICATIONS OPERATING POWER 16.5 VAC, 40 or 50 VA Transformer AUXILIARY POWER w/40 or 50 VA Transformer 12 VDC Regulate

Strany 80 - XXIII. SPECIFICATIONS

NX-8E CONTROL 7Start/End Programming and End Downloading- A report can be sent when local programming is started and ended. A report can also be sen

Komentáře k této Příručce

Žádné komentáře